Dry Contacts The PM2X series SPD device is provided with dry contacts. The connection
for the dry contacts is provided by 24-inch wire leads. The wire leads are
22 AWG stranded copper wire. See Table 5 for wire color and contact state.
The unpowered state shall be closed between the red wire (common) and
the yellow wire (normally closed). This is also the alarm condition. The
opposite state, closed between the red wire (common) and the blue wire
(normally open), indicates that power is on to the unit and that no alarm
condition exists (See Table 5). These dry contact leads can be used for
remote indication of the SPD operating status to a computer interface board
or emergency management system. Also, these dry contact leads are
designed to work with the SPD remote monitor option described below.
The dry contacts are designed for a maximum voltage of 24 Vdc / 24 Vac
and a maximum current of 2 A. Higher energy applications may require
additional relay implementation outside the SPD. Damage to the SPD’s
relay caused by use with energy levels in excess of those discussed in this
instruction bulletin are not covered by warranty. For application questions,
call APC Technical Support at 1-800-800-4272.
Table 5: Dry Contact Configuration
Wire Color Normal Contact State
1
1
Normal state shown is with AC power on the SPD.
Blue Closed
Red Common
Yellow Open