34001813EN/AE - Page 12
2. Installation
2.1 Location
2.2 Layout of cabinets
To ensure correct ventilation, leave nothing
on top of the UPS.
Leave one meter of free space in front of the
UPS for door opening.
The cabinet rests on four cylindrical feet,
40 mm in diameter, positioned in the four
corners of the cabinet to spread the weight.
If 500 mm of free space is not maintained
above the UPS, abnormal temperature rise
may occur.
The UPS must be installed in a room with
restricted access (qualified personnel
only).
(*) The UPS can operate correctly back to the
wall, but it is preferable to leave some space
for easier maintenance.
0 - 600 mm*
IO
3s
?
~
>500 mm
>1000 mm
IO
3s
?
~
I
O
3s
?
~
UPS cabinet
UPS cabinet
Battery cabinet
Battery cabinet 2
Battery cabinet 1