System Specifications
990-4053
Installation Guide APC Silcon 480kW 400V UPS 69
7.0 System Specifications
7.1 Technical Data
7.2 Dimensions / Weight
Voltage 3x380/400/415V
Input Voltage tolerance
Normal operation
Bypass operation
+15%
+10% (standard)
+4, 6, 8% (programmable)
Frequency 50Hz/60Hz
+6 standard
+0.5-8% (programmable)
Input power factor load 25% minimum 0.97
load 100% minimum 0.99
Current distortion Max. 5%
Output Voltage 3x380/400/415V
Voltage tolerance +
1% static symmetrical load
+3% static symmetrical load
+5% 0-100% load step
Voltage distortion max. 3% linear load
max. 6% non-linear load
Load power factor 0.9 lead to 0.8 lag
Frequency 50Hz/60Hz (mains synchronized)
+0.1% free-running
Overload capacity
Mains operation
Mains operation
Battery operation
Bypass operation
200% - 60 seconds
125% - 10 minutes
150% - 30 seconds
125% - continuous
General Ambient temperature 0-40
o
C (Temperatures above 25
o
C will
reduce battery lifetime)
Humidity
Protection class
Safety
Emission and Immunity
Static bypass switch
Auto restart
Economy mode
Max. 95% non-condensing
IP30
EN 50091-1
CE Mark
EN 50091-2
Built-in
Programmable
Programmable
Type 480kW
Height [mm] 1800
Width [mm] 1900
Depth [mm] 800
Weight [kg] 1800
Page view 68