23Pumped Refrigerant System Operation and Maintenance
Group Configuration
Group settings determine which modules are available in each group and how the groups should operate.
Modify a Cooling Module (CM) ID
Path: Main > Cooling Modules > Select CM > Configuration > Modify CM ID
RDU ID.
The unique identification number of the RDU.
Group #. Select a new Group number.
CM #. Select a new CM number.
Assign CM. Select to apply the changes to the selected CM. Once selected, the confirmation screen
comes up. Select Yes or No.
View the groups
Path: Main > Groups
Select Group.
Select the group you want to view.
CM List. From the group number you selected, you can view the CMs by ID number.
Number of Units. Select the number of CMs you expect to be in the group. The Group
Communications Loss alarm is initiated if the CMs detect less or more CMs than this value.
Unassign CMs
Two menu paths are available to unassign cooling modules.
1. From this menu, select the CM ID to unassign. Press the
ENTER key and Select Ye s.
Path: Main > CMs in Network > All Assigned CMs
2. From this menu, press the ENTER key and select.
Path: Main > Cooling Modules > Select CM > Configuration > Unassign CM
Configure Modbus
Path: Main > Configure Modbus
Modbus.
Enable or Disable the Modbus communication protocol.
Target Id. Each Modbus device must have a unique target identification number. Enter a unique number
from 1 to 247 for the RDU.
Baud Rate. 9600 bps.
CAUTION
HAZARD TO EQUIPMENT OR PERSONNEL
All work must be performed by American Power Conversion (APC
®
) by Schnieder Electric
authorized personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.