39Pumped Refrigerant System Operation and Maintenance
Persistent Receiver Pumped
Dry
Critical • Verify that there is adequate refrigerant in the system.
• Verify that the Cooling Modules are functioning properly.
• If the problem persists, contact Technical Support.
Primary Power Source
Failure
Warning • Ensure that the power source is connected properly and within
specifications.
• If the problem persists, contact Technical Support.
Secondary Power Source
Failure
Warning • Ensure that the power source is connected properly and within
specifications.
• If the problem persists, contact Technical Support.
Pump 1 Discharge Pressure
Sensor Fault
Critical • Make sure the pressure sensor is connected properly.
• If the problem persists, contact Technical Support.
Pump 1 Fault Warning • Contact Technical Support.
Pump 1 High Head Pressure Warning • Contact Technical Support.
Pump 2 Discharge Pressure
Sensor Fault
Critical • Make sure the pressure sensor is connected properly.
• If the problem persists, contact Technical Support.
Pump 2 Fault Warning • Contact Technical Support.
Pump 2 High Head Pressure Warning • Contact Technical Support.
Pumps Vapor Locked Warning • Contact Technical Support.
Pump Outlet Temperature
Sensor Fault
Warning • Make sure the temperature sensor is connected properly.
• If the problem persists, contact Technical Support.
RDU Communication Fault Critical • Contact Technical Support.
Receiver Pumped Dry Warning • Verify that there is adequate refrigerant in the system. Add refrigerant if
necessary.
• If the problem persists, contact Technical Support.
Refrigerant Loss Detected Critical • A refrigerant leak has been detected.
• Identify the source of the leak.
• Have the leak repaired and the refrigerant replaced.
• For assistance, contact Technical Support.
Refrigerant Loss Detection
Disabled
Warning • At least one of the following conditions has occurred:
- Refrigerant was added to the system
- One or more CMs have been added or removed from the system.
- One or more CMs have been placed into Standby, Stop or Maint mode.
• If the change is permanent, the refrigerant leak detector must be
recalibrated.
• For assistance, contact Technical Support.
Starting Conditions Not
Satisfied
Warning • Ensure the chilled water temperature is within specifications.
• If the problem persists, contact Technical Support.
System Stop Critical Check for other alarms (Water Leak Detected, Persistent Receiver
Pumped Dry, Pump Fault, Pumps Vapor Locked).
• If the problem persists, contact Technical Support.
Subcooler Outlet
Temperature Sensor Fault
Warning • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
Temperature/Humidity
Sensor Duplicate CAN
Address
Warning • Inspect the DIP switches on the temperature/humidity sensors and
ensure that all the settings are unique.
Temperature/Humidity
Sensor N Added
Informational • Notification that the addition of the new sensor has been recognized by
the RDU.
Temperature/Humidity
Sensor N Removed
Informational • Notification that the removal of the sensor has been recognized by the
RDU.
Alarm Message Severity Action Required