4 - APC UNIVERSAL TRANSFER SWITCH CONFIGURATION
Table 4-3 Typical UTS6H Circuit Setup with UPS
Typical UTS Circuit Setup with UPS
PARAMETER
CIRCUIT
I
CIRCUIT
2
CIRCUIT
3
CIRCUIT
4
CIRCUIT
5
CIRCUIT
6
Load Type
Other (con-
densate
pump)
Sump
pump
Boiler Computer
Security
System
Refrigerator
Source GEN EITHER GEN EITHER EITHER GEN
Delayable Yes Yes No Yes Yes Yes
Max time off (min) 30 1 30 5 60 30
Min time on (min) 30 2 30 5 60 15
Security Mode Off Off Off Off Off Off
Amp Rating(A) 15 15 15 15 15 15
Note: UPS power output cord shall be attached to “UPS” inlet port of the UTS6H.
Table 4-4 - Typical UTS6H System Setup with UPS
Typical UTS6H System Setup with UPS
Bypass mode No
Load shedding? On
Voltage sensitivity Medium
Time Management On
Reset Energy Meter No
System Test No
Backup1 Source Type Generator (1)
GEN power rating 1700 (2)
GEN SRGE Overload Time 0 seconds
GEN Start Mode manual
Backup2 Source Type UPS (3)
GEN power rating 2100 (4)
GEN SRGE Overload Time 0 seconds
Reset to default no
Notes:
Generator:1. Corresponds to 240VAC GEN port on UTS6H.
GEN Power Rating (Backup1)2. : Set to 1,700 watts to account for 100 watt power consumption of load
balancing transformer.
UPS:3. Corresponds to UPS inlet port on UTS6H.
GEN Power Rating (Backup2):4. Corresponds to 1,700 watts of MCHP power PLUS UPS power rating (in this
case 400 watts).