Figure 8-2 Hydronic
Freewatt PLUS
System Distribution Piping Schematic with Zone Valves and
Priority DHW Pump
8.3 freewatt PLUS
System Piping
Place equipment in proper locations.
Con gure system piping to connect boiler and HONDA
MCHP to distribution piping.
Hydronic
freewatt PLUS
piping con guration is
modi ed primary-secondary, allowing heat from MHCP
unit be injected into return piping upstream from
freewatt PLUS
boiler. Con guration ensures coldest
return water be delivered to MCHP unit’s hydronic
hybrid integration (HI) module.
8 - PLACING THE SYSTEM
Figure 8-2 shows
freewatt PLUS
distribution piping
schematic for system zoned with zone valves for
heating zones and priority pump for indirect water
heater zone. Con guration of heating zones, boiler
and MCHP heat sources shown is mandatory for proper
operation of
freewatt PLUS
System.
See piping schematics in Section 17 for circulator zoned
systems, valve zoned systems and systems with air
handlers.