Command Reference: Outlet Commands
Command Line Interface (CLI) User’s Guide 21
rebootduration
Syntax (to read the reboot duration):
rebootduration [outlet|range][,outlet|range...]
Syntax (to set the reboot duration):
rebootduration outlet|range[,outlet|range...]:time
Description: Set or read the reboot duration (the
time in seconds that an outlet will remain off
before restarting). If you do not specify any outlets,
the reboot duration settings of all outlets to which
you have access are read. To set the reboot
duration, you must specify one or more outlets.
Parameters:
Output format, reading reboot duration:
OK
outlet_number: outlet_name: Reboot duration is
time seconds.
Output format, setting reboot duration:
OK
outlet_number: outlet_name: Setting reboot
duration to time seconds.
Error Messages: E101, E104
outlet An outlet name or number. If you specify a
name that contains a space character, you must
enclose the name in quotation marks.
range A range of outlet numbers, with a hyphen
separating the starting number from the
ending number.
time The reboot duration in seconds to set for the
specified outlets.