Command Reference: Switched Rack PDU
Command Line Interface (CLI) User’s Guide 25
lowloadwarning
Syntax (to read the low-load warning threshold):
lowloadwarning [phase_number]
Syntax (to set the
low-load warning
threshold):
lowloadwarning phase_number current
Description: Set or read the low-load warning
threshold.
Parameters:
Access:
Administrator or device manager
(device-only user).
Output format, reading the low-load warning
threshold:
OK
Low load warning threshold is currentA.
Output format, setting the low-load warning
threshold:
OK
Setting low load warning threshold for
phase_number to currentA.
Error Messages: E101, E104
name
Syntax:
name outlet new_name
Description: Assign a name to an outlet or a
system name to the Switched Rack PDU.
Access: Administrator or device manager
(device-only user).
Parameters:
Output Format:
OK
outlet: Setting name to new_name
Error Message: E101
phase_number The number (1, 2, or 3) of the phase
whose low-load warning threshold
will be read or set. The default is 1.
current The threshold, in amps, to set for the
phase specified as phase_number.
outlet An outlet number or, to specify the system
name of the Switched Rack PDU, the
string
master (not case-sensitive).
new_name A name to assign to the outlet or, if master
was specified as outlet, the system name
to assign to the Switched Rack PDU. The
name can be up to 23 printable ASCII
characters. If the name contains one or
more spaces, you must enclose the name
in quotation marks.
Page view 28