Command Reference: Switched Rack PDU
Command Line Interface (CLI) User’s Guide 27
overloadalarm
Syntax (to read the overload alarm threshold):
overloadalarm [phase_number]
Syntax (to set the overload alarm threshold):
overloadalarm phase_number current
Description: Set or read the overload alarm
threshold.
Parameters:
Access:
Administrator or device manager
(device-only user).
Output format, reading the overload alarm
threshold:
OK
Overload alarm threshold for phase_number is
currentA.
Output format, setting the overload alarm
threshold:
OK
Setting alarm threshold for phase_number to
currentA
Error Messages: E101, E104
phase_number The number (1, 2, or 3) of the phase
whose overload alarm threshold you
want to read or set. The default is
phase 1.
current The threshold, in amps, to set for the
phase specified as phase_number.