Parallel connected UPS (continued)
Main status bits of system operations
Normal : inverter powers load and maximum bit 4C4 = 1
backup time available
Danger : inverter does not power load bit 4C6 = 1
Downgraded : malfunction or environment fault bit 4C5 = 1
Load on battery : load on battery power bit 4C7 = 1
Operating modes
The following section describes the
different states of a
MGE
TM
Galaxy
TM
6000 UPS and
the addresses of the bits in the
system data array.
Normal operation
Normal: bit 4C4 = 1
Danger: bit 4C6 = 0
Downgraded: bit 4C5 = malfunction dependent
Load on battery: bit 4C7 = 0
Q1 closed: bit 40E = 1
Rectifier/charger on: bit 408 = 1
QF1 closed: bit 400 = 1
Inverter connected: bit 484 = 1
Q5N closed: bit 498 = 1
Load on battery
Normal: bit 4C4 = 1
Danger: bit 4C6 = 0
Downgraded: bit 4C5 = malfunction dependent
Load on battery: bit 4C7 = 1
Q1 indifferent: bit 40E = X (N/A)
Rectifier/charger off: bit 408 = 0
QF1 closed: bit 400 = 1
Inverter connected: bit 484 = 1
Q5N closed: bit 498 = 1
Disconnected
Normal: bit 4C4 = 0
Danger: bit 4C6 = 1
Downgraded: bit 4C5 = X (N/A)
Load on battery: bit 4C7 = X (N/A)
Q1 indifferent: bit 40E = X (N/A)
Rectifier/charger indifferent: bit 408 = X (N/A)
QF1 indifferent: bit 400 = X (N/A)
Inverter not connected: bit 484 = X (N/A)
Q5N open: bit 498 = 0