APC MGETM GALAXYTM 6000 User Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
6739389EN/FB - Page 35
System information (continued)
41B: battery equalization (0=not
active/1=active)
The rectifier-charger has been
manually switched to equalization
mode, to equalize battery cell
voltages. This action stops all
inverters powered by the battery (if
they were not already stopped).
41E: operation on engine-
generator set (0=not activated /
1=activated)
Indicates that the rectifier-charger
is supplied by an engine-generator
set and not by the normal Mains 1
power supply.
Word address: 44
440: inverter stack overload
(0=no/1=overload)
Indicates an overload condition due
to a load power factor exceeding 0.9.
441: major inverter fault (0=no/
1=fault)
Informs the user of an inverter fault
requiring after-sales servicing.
445: inverter output current
limiting (0=no/1=active)
Informs the user that an overload
exceeding 1.6 In has occurred at
the output: the inverter stops
operating.
446: inverter thermal overload
(0=no/1=overload)
Informs the user that the output is
overloaded by a factor between 1
and 1.6 In: the inverter stops
operating.
44C: outside contact (0=not
activated/1=activated)
Normally open switch. Initiates the
actions that have been configured
using the after-sales "Soft Tunor"
computer software. Possible
actions when activated:
no action;
inverter off;
forced inverter shutdown;
conditional inverter shutdown;
frequency change (when
powering on the unit) with respect
to the frequency configured by the
after-sales "Soft Tunor" computer
software (i.e. 50Hz to 60Hz or vice
versa).
MGE
TM
Galaxy
TM
6000 UPS.
484: inverter connected to the
load (0=not connected/
1=connected)
The inverter is operating and
powers the load.
485: inverter off disable
(0=enabled/1=disabled)
The inverter off command is
disabled.
486: synch with Mains 2 (0=not
synch/1=synch)
The inverter may operate without
its frequency synchronized to that
of Mains 2 (i.e. free-running
operation); in this case, it operates
at an accurate (within 0.05 Hz)
fixed frequency. Alternatively, the
inverter may be operated with its
frequency synchronized to that of
Mains 2.
487: transfer fault (0=no fault/
1=fault)
Informs the user of a fault on the
static switch, used to transfer the
load between Mains 2 and inverter
output. After-sales servicing is
required.
48A: Mains 2 voltage outside
tolerances (0=normal / 1=outside
tolerances)
Indicates to the user that the Mains
2 backup power supply voltage is
outside tolerances. A transfer of the
load to the Mains 2 backup power
supply will result in a 0.8 second
interruption in the supply of power
to the load or may not take place.
48D: emergency off switch
(0=not activated/1=activated)
Normally-closed switch connected
to the units. When activated, the
rectifier-charger circuits and the
inverters stop operating. The "QF1"
battery circuit breaker is also
opened.
If the "emergency off" also tripped
the protection devices to
disconnect the units from Mains 1
and Mains 2, the load no longer
receives power and the units are
completely disconnected.
44D: emergency off switch
(0=not activated/1=activated)
Normally-closed switch connected
to the units. When activated, the
rectifier-charger circuits and the
inverters stop operating. The "QF1"
battery circuit breaker is also
opened. If the "emergency off" also
trips the protection devices to
disconnect the units from Mains 1
and Mains 2, the load no longer
receives power and the units are
completely disconnected.
Word address: 46
464: forced inverter shutdown
(0=not activated / 1=activated)
Indicates to the user that a
shutdown of the inverter will result
in transfer of the load to Mains 2
with the risk of a 0.8 second
interruption in the supply of power
to the load.
465: frequency conversion
(0=not activated / 1=activated)
Indicates that the
MGE
TM
Galaxy
TM
6000 UPS is
operating as a frequency converter
between the input and the output
(50 Hz / 60 Hz).
466: conditional inverter
shutdown (0=not activated /
1=activated)
Indicates to the user that a
shutdown of the inverter will take
place only if the load transfer
conditions to Mains 2 are correct to
avoid an interruption in the supply
of power to the load.
Word address: 48
480: inverter overload (0=no/
1=overload)
Informs the user that the load is
drawing more than the rated UPS
output.
482: ventilation of the battery
cabinets (0=no fault / 1=fault)
Indicates to the user that ventilation
in a battery cabinet is incorrect due
to a fan fault or shutdown. This fault
does not result in UPS shutdown.
This information is available only on
European versions of the
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38