APC MGETM GALAXYTM 6000 User Manual Page 30

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 29
Page 30 - 6739389EN/FB
System information (continued)
Voltage fields
Legend:
yes: available in this cubicle;
no entry: not available.
measured voltage units JBUS address type
hex. word unitary parallel SS
U12 Mains 1 V 140 yes yes
U23 Mains 1 V 141 yes yes
U31 Mains 1 V 142 yes yes
U1N inverter V 143 yes yes
U2N inverter V 144 yes yes
U3N inverter V 145 yes yes
U12 inverter V 146 yes yes
U23 inverter V 147 yes yes
U31 inverter V 148 yes yes
U1N Mains 2 V 149 yes yes
U2N Mains 2 V 14A yes yes
U3N Mains 2 V 14B yes yes
U12 Mains 2 V 14C yes yes
U23 Mains 2 V 14D yes yes
U31 Mains 2 V 14E yes yes
U1N load V 14F yes yes yes
U2N load V 150 yes yes yes
U3N load V 151 yes yes yes
U12 load V 152 yes yes yes
U23 load V 153 yes yes yes
U31 load V 154 yes yes yes
U battery V 155 yes yes
power measurements units JBUS address type
hex. word unitary parallel SS
P1 (load active power) kW 180 yes yes yes
P2 (load active power) kW 181 yes yes yes
P3 (load active power) kW 182 yes yes yes
S1 (load apparent power) kVA 183 yes yes yes
S2 (load apparent power) kVA 184 yes yes yes
S3 (load apparent power) kVA 185 yes yes yes
P (load active power) kW 186 yes yes yes
S1 (load apparent power) kVA 187 yes yes yes
% inverter load - 188 yes yes yes
power factor - 189 yes yes yes
frequencies units JBUS address type
measurements hex. word unitary parallel SS
F Mains 1 dHz 1A0 yes yes
F inverter dHz 1A1 yes yes
FMains 2 dHz 1A2 yes yes
F load dHz 1A3 yes yes yes
Power fields
Frequency fields
Legend:
yes: available in this cubicle;
no entry: not available.
Page view 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 36 37 38

Comments to this Manuals