Smart-UPS SC / Smart-UPS Runtime @ Full Load Capacity (minutes)
Plug and Receptacle Types
Form APC Part Number
Capacity
(Volt Amps/Watts)
Standard
Runtime
Input Output
Rack
mount
SC450RMI1U* 450 / 280 6
IEC-320 C14 (4) IEC 320 C13SUA750RMI2U 750 / 480 5
SUA1500RMI2U 1500 / 980 7
SUA2200RMI2U 2200 / 1980 5
IEC-320 C20
(8) IEC 320 C13,
(1) IEC 320 C19
SUA3000RMI2U 3000 / 2700 3
Tower
SC450RMI1U* 450 / 280 6
IEC-320 C14
(4) IEC 320 C13
SUA750I 750 / 500
5
(6) IEC 320 C13
SUA1500I 1500 / 980 (8) IEC 320 C13
SUA2200I 2200 / 1980
IEC-320 C19
(8) IEC 320 C13,
(1) IEC 320 C19
SUA3000I 3000 / 2700
Smart-UPS XL Runtime @ Full Load Capacity (minutes)
Form APC Part Number
Capacity
(Volt Amps/Watts)
Standard
Runtime
Standard + (1) External
Battery Pack
Standard + (2) External
Battery Pack
APC Battery Pack
Part Number
Input Output
Rack
mount
SU1400RMXLIB3U 1400 / 1050 7 35 75 SU24R2XLBP
IEC-320 C14
(8) IEC 320 C13
SUA2200RMXLI2U 2200 / 1580 7 36 76
SUA48RMXLBP3U
(9) IEC 320 C13
SUA3000RMXLI3U 3000 / 2700 6 21 50
IEC-320 C20 British
BS1363A
Schuko CEE 7/EU1-16P
(8) IEC 320 C13,
(1) IEC 320 C19
Tower
SUA1000XLI 1000 / 800 10 65 88 SUA24XLBP
IEC-320 C14
(8) IEC 320 C13
SUM1500RMXLI2U 1500 / 1425 12 38 69
SUM48RMXLBP2U
(9) IEC 320 C13
SUM3000RMXLI2U 3000 / 2850 3 16 32 IEC-320 C20
(7) IEC 320 C13,
(1) IEC 320 C19
Smart-UPS RT* Runtime @ Full Load Capacity (minutes)
Form APC Part Number
Capacity
(Volt Amps/Watts)
Standard
Runtime
Standard + (1) External
Battery Pack
Standard + (2) External
Battery Pack
APC Battery Pack
Part Number
Input Output
Rack
mount
SURT1000RMXLI 1000 / 700 10 53 99 SURT48RMXLBP IEC-320 C14 (6) IEC 320 C13
SURT3000RMXLI 3000 / 2100 14 57 102
SURT192RMXLBP
IEC-320 C20, British
BS1363A, Schuko CEE
7/EU1-16P
(8) IEC 320 C13,
(2) IEC 320 C19
SURT5000RMXLI 5000 / 3500 5 27 50 Hard Wire 3-wire
(8) IEC 320 C13,
(2) IEC 320 C19
SURT10000RMXLI 10000 / 8000 4 11 20
Hard Wire 3-wire,
Hard Wire 5-wire
(1) Hard Wire 3-wire,
(4) IEC 320 C13,
(4) IEC 320 C19
Tower
SURT1000XLI 1000 / 700 10 53 99 SURT48XLBP IEC-320 C14 (6) IEC 320 C13
SURT3000XLI 3000 / 2100 14 57 102
SURT192XLBP
IEC-320 C20 British
BS1363A
Schuko CEE 7/EU1-16P
(8) IEC 320 C13,
(2) IEC 320 C19
SURT5000XLI 5000 / 3500 5 27 50 Hard Wire 3-wire
(8) IEC 320 C13,
(2) IEC 320 C19
SURT10000XLI 10000 / 8000 4 11 20
Hard Wire 3-wire,
Hard Wire 5-wire
(1) Hard Wire 3-wire,
(4) IEC 320 C13,
(4) IEC 320 C19
Symmetra / Symmetra LX* Runtime @ Full Load Capacity (minutes)
Form APC Part Number
Capacity
(Volt Amps/Watts)
Standard
Runtime
Standard + (1) External
Battery Frame
Standard + (2) External
Battery Frame
APC Battery Frame
Part Number
Input Output
Rack
mount
SYH4K6RMI 4000 / 2800 13 51 92
SYRMXR4B4I
Hard Wire 3-wire
(8) IEC 320 C13,
(2) IEC 320 C19
SYH6K6RMI 6000 /4200 13 38 65
SYA8K8RMI 8000 / 5600 7 72 143
SYARMXR9B9I
(1) Hard Wire 3-wire,
(8) IEC 320 C13,
(6) IEC 320 C19
SYA12K16RMI 12000 / 8400 8 50 95
Hard Wire 3-wire,
Hard Wire 5-wire
(1) Hard Wire 3-wire,
(8) IEC 320 C13,
(10) IEC 320 C19
SYA16K16RMI 16000 / 11200 8 39 72
Tower
SYA8K8I 8000 / 5600 7 72 143
SYAXR9B9I
Hard Wire 3-wire
(1) Hard Wire 3-wire SYA12K16I 12000 / 8400 7 50 95
Hard Wire 3-wire,
Hard Wire 5-wire
SYA16K16I 16000 / 11200 8 39 72
* Models are rack/tower convertible
For the most recent sizing information and additional runtime options consult www.apc.com