NetShelter VL Enclosure—Unpacking, Installation, and Customization 26
3. The enclosures can be joined so that their centers are 24 in or 600 mm apart. Align the enclosures
to use the appropriate holes on the front and rear of the enclosures and secure the enclosures
using one M5 x 12 flat-head screw per bracket.
4. If enclosures are joined together on 24-in centers, there is a gap between them. APC offers
optional baying trim (AR7600) to cover the gap between the enclosures. The trim snaps into
place without tools and can be installed after the units are joined together and have equipment
installed in them.
Note: The 600-mm enclosures join together without a gap when joined using the
inner-most set of holes on the joining brackets.
5. Reconnect the grounding wires, and reinstall the doors, if needed.
See “Installing the doors” on page 13.
To connect a NetShelter VL enclosure to a NetShelter SX, VX, or VL enclosure, APC offers a separate
joining kit (AR7601 for enclosures with 600-mm centers or AR7602 for enclosures with 24-in centers).
When using the joining kit, the NetShelter VL enclosure will be inset by 33.2 mm (1.3 in) from the
NetShelter SX, VX, or VS enclosure.