NetShelter SX Enclosure: Unpacking, Installation, and Customization4
Unpacking
Unpacking the enclosure
Heavy: Use at least two people to unpack the enclosure.
Warning: To prevent the enclosure from tipping over after installation:
Stabilize the enclosure before installing the components. See “Rack stabilization
options” on page 9.
Do not extend components on sliding rails out from the enclosure until you have
installed three or more pieces of similar equipment, or the stabilizer plate or bolt-down
brackets are installed. See “Rack stabilization options” on page 9.
• Do not extend more than one component from the enclosure at a time.
• Load the heaviest components first, and place them toward the bottom of the enclosure to
prevent the enclosure from becoming top-heavy.
• Use caution when moving an empty enclosure on its casters; the enclosure may be unstable
when pushed or pulled from the side. Push the enclosure from the front or back when
moving it on its casters. For extra stability, load 158 kg (350 lbs) of equipment into the
bottom of the enclosure before moving it on its casters.
1. Move the shipping pallet to a firm, level surface in an open area. Inspect the enclosure for visible
signs of shipping damage. If you detect shipping damage, contact APC Customer Support at the
number listed on the yellow label on the front of the enclosure or on the back cover of this
manual.
2. See the label on the packaging to determine where to cut the wrapping. Using sturdy shears or a
utility knife, carefully remove the plastic stretch wrap surrounding the enclosure.
Note: Save the bag containing the warranty card and installation manual.
3. Remove the four cardboard corner protectors.
4. Remove the two pallet-mounting brackets that anchor the enclosure to the shipping pallet, using a
13-mm wrench (not provided).
Note: Save the pallet-mounting brackets if you plan to bolt the enclosure to the floor.
See “Rack stabilization options” on page 9.