23InRow RC Operation and Maintenance
Entering Fluid Temperature
Sensor Fault
Warning • Make sure the sensor is connected properly.
• Replace the sensor.
• For assistance, contact APC Customer Support. See the back cover
of this manual for contact information.
Fan #n Fault Warning • Make sure all air intakes are clear of any blockage.
Note: Fans are numbered sequentially, starting with Fan 1 at the
bottom.
• For assistance, contact APC Customer Support. See the back cover
of this manual for contact information.
Fan Power Supply Left Fault Warning • Replace the power supply.
• For assistance, contact APC Customer Support. See the back cover
of this manual for contact information.
Fan Power Supply Right Fault Warning • Replace the power supply.
• For assistance, contact APC Customer Support. See the back cover
of this manual for contact information.
Filter Sensor Fault Warning For assistance, contact APC Customer Support. See the back cover
of this manual for contact information.
Fluid Flowmeter Fault Critical • If a leak exists, fix the problem.
• Make sure the supply and return chilled water pipes are connected
properly, fluid is flowing from the chiller to the unit, and the
electrical connections to the flowmeter are correct.
Displayed Alarm Message Severity Action Required
na1989a
Return Temperature Sensor
Supply Temperature Sensor