APC NetworkAIR CM Series: Optional Features 9
Optional Features
The following optional features are available on the CM Series unless
otherwise noted. Certain combinations of options may not be available.
Emergency/
environmental
Smoke detector(s). A smoke detector shall ship loose for field installation
into ductwork. Upon detecting smoke concentration, if equipped with a
microprocessor, an audible and visual alarm will be activated and the unit
will immediately shut-down.
Firestat. A Firestat is available for installation into ductwork. If the return
air temperature reaches 125° F (52° C), the air conditioner will be turned off
and both an audible and visual alarm will be activated if equipped with a
microprocessor.
Essential/non-essential lockout. When facilities have limited backup
power capacity, this lockout prevents the operation of electrical loads that are
not essential for continued site operation.
Microprocessor
controller
The microprocessor controller provides state of the art control for a wide
variety of environmental applications including the demanding requirements
of data centers, control rooms, clean rooms, switch rooms, MRI facilities,
CAT scan facilities and UPS Rooms. Operator Interface is provided by the
four-line, 80-character backlit LCD display. A user-friendly menu structure
along with clearly defined prompts allow the operator to easily move about
the program. Within the configuration menu the operator will find numerous
selections allowing the CM to be tailored to meet specific requirements.
Status. Complete status monitoring is provided within the status menu of the
microprocessor controller.
Available information includes:
Alarms. Quick access to any alarm condition is facilitated through the menu
structure. The alarm key acts as a hot key, providing immediate access to the
alarm display menu. Presence of a new alarm will sound the audible alarm.
The red alarm LED on the display panel will remain illuminated until all
alarms have been cleared. The temperature and humidity alarm setpoints are
adjustable.
Alarm annunciations include:
Current temperature Cooling status
Current humidity Heating status
Temperature setpoint Humidification status
Humidity setpoint Dehumidification status
Loss of airflow High temperature
Clogged filter Low temperature
High head pressure High humidity
Low suction pressure Low humidity
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 72 73