APC NetworkAIR CM Series: Drycooler 55
Drycooler
Glycol-cooled drycooler—physical data
MODEL TEMP. AIR QUALITY FAN CONNECTION WEIGHT
TONNAGE AMBIENT CFM
M
3
/H
QUANTITY HOT GAS LIQUID Lbs Kg
1 ton 95° F 2,400 4,100 1 5/8" 5/8" 96 44
1.5 ton 95° F 2,400 4,100 1 7/8" 5/8" 96 44
2 ton 95° F 2,100 3,600 1 5/8" 5/8" 114 52
3 ton 95° F 5,050 8,600 1 1-1/8" 5/8" 180 82
4 ton 95° F 6,450 11,000 1 1-1/8" 5/8" 260 118
5 ton 95° F 6,450 11,000 1 1-1/8" 5/8" 260 118
Glycol cooled drycooler—electrical data
MODEL TEMP. 208-230/1/60 208-230/3/60 460/3/60
TONNAGE AMBIENT FLA MCA MOP FLA MCA MOP FLA MCA MOP
1 ton 95° F 2.0 2.5 15 N/A N/A N/A N/A N/A N/A
1.5 ton 95° F 2.0 2.5 15 N/A N/A N/A N/A N/A N/A
2 ton 95° F 2.0 2.5 15 N/A N/A N/A N/A N/A N/A
3 ton 95° F 3.4 4.3 15 2.6 3.3 15 1.3 1.6 15
4 ton 95° F 3.9 4.9 15 2.6 3.3 15 1.3 1.6 15
5 ton 95° F 3.9 4.9 15 2.6 3.3 15 1.3 1.6 15
Comments to this Manuals