Introduction: Intake and Exhaust Vents
NetworkAIR
®
ACPA4000 User Manual 7
Assemble the ceiling adapter
Attach the air deflector to the exhaust side of the ceiling
adapter using three M6 nuts.
The air deflector must face away from the air intake and obstructions such as a wall or
piping. Failure to position it in this way will reduce cooling capacity and could cause unit
alarms.
Install the adapter in a drop ceiling
Use the ceiling adapter to provide an intake and exhaust outlet for the condenser.
1. Determine a location to install the ceiling adapter, and remove the ceiling tile in your chosen
location. Save it for a future step.
2. Place the ceiling adapter into the ceiling tile grid.
Caution
Note
There should be no less than 12 inches (30.5 centimeters) of open space above the
ceiling adapter opening, so exhaust air is not blocked.