APC NETWORKAIR ACPA4000 User Manual Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
Operation: Responding to Alarms
30 NetworkAIR
®
ACPA4000 User Manual
Alarm messages
Alarm Message Action Required
High head pressure Ensure condenser exhaust air diverter is not blocked, facing a wall, or
pointed at the condenser air inlet.
Check the condenser inlet filter for cleanliness.
Supply temperature
high
Alarm set point may be too low.
Check to see if unit is cooling. Verify at least a 15° F (9.4° C)
temperature difference between the supply and return temperatures.
Supply temperature
low
Alarm set point may be too high.
Front airflow may be obstructed. Check return filter and front unit grills
for free air movement.
Cooling set point may be too low to allow for at least a 20° F (6.6°C)
temperature differential between return and supply temperatures, based
on the cooling set point. Example: A set point of 70°F (21.1°C) could
have a supply temperature as low as 50°F (10°C).
Return temperature
high
Alarm set point may be too low.
Unit capacity may be too small for room load.
Ensure that return air coming back to the unit is not from a direct heat
source, equipment discharge fan, or room supply duct.
Alarm delay may be too short. Sufficient time must be allowed to let the
unit bring the temperature in the space under control. This is especially
true with new equipment start-ups.
Return temperature
low
Alarm set point may be too high.
Verify that the return air is not coming from a cold air supply source
like a room discharge duct.
There should not be any obstructions near the grill front that could re-
divert supply air back to the return air grill.
Page view 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 47 48

Comments to this Manuals

No comments