Operation: Responding to Alarms
NetworkAIR
®
ACPA4000 User Manual 31
Remote temperature
high
Alarm set point may be too low.
Check that the sensor is not near a direct heat source like an equipment
discharge fan, a room supply duct, a window, direct sunlight, or a room
entrance.
Unit capacity may be too small for room load.
Check that the unit is cooling. Verify that there is at least a 15° F
(9.4° C) temperature difference between supply and return.
Remote temperature
low
Alarm set point may be too high.
Verify that the return air is not coming from a cold air supply source
like a room discharge duct or an open window.
Remote humidity
high
Alarm set point may be too low.
Alarm delay may be too short. Sufficient time must be allowed to let the
unit bring space humidity under control. This is especially true with
new equipment start-ups.
Remote sensor may be located near a moisture source like an open sink,
a window, or an entrance to an unconditioned space.
Unit capacity may be too large for space. Reduce fan speed to low.
Remote humidity low Alarm set point may be too high.
Air filter clogged Change the filter.
Water collection pan
full
Check the drain line.
User contact 1 alarm
Check the connected device.
User contact 2 alarm Check the connected device.
User contact 3 alarm Check the connected device.
Unit shutdown via
remote stop
Verify remote stop.