18
Tower and 5U Rack Mount Models - 3000 & 5000 VA Models
Typical On-Battery Run Time Versus Load, in Hours
Load 3000 VA Internal Battery 3000 VA w/ 1 Battery Pack 5000 VA Internal Battery
100 VA 3.80 8.18 7.17
150 VA 3.05 6.57 5.95
200 VA 2.35 5.42 5.04
300 VA 1.83 4.08 3.88
400 VA 1.40 3.22 2.96
500 VA 1.12 2.62 2.37
600 VA 0.90 2.18 1.92
800 VA 0.58 1.6 1.40
1000 VA 0.43 1.22 1.06
1200 VA 0.33 0.97 0.83
1400 VA 0.27 0.70 0.65
1600 VA 0.22 0.58 0.54
2000 VA 0.17 0.42 0.39
2200 VA 0.13 0.37 0.33
2500 VA 0.11 0.30 0.26
3000 VA 0.08 0.22 0.19
3500 VA - - 0.16
4000 VA - - 0.13
4500 VA - - 0.11
5000 VA - - 0.09
3U Rack Mount Models - 2200 & 3000 VA Models
Typical On-Battery Run Time Versus Load, in Hours
Load NS2200RM
SU2200RM
(3U)
NS3000RM
SU3000RM
(3U)
50 VA 5.60 4.53
75 VA 4.73 3.93
100 VA 4.08 3.45
150 VA 3.15 2.75
200 VA 2.53 2.25
250 VA 2.10 1.88
300 VA 1.77 1.60
350 VA 1.52 1.40
400 VA 1.32 1.23
450 VA 1.16 1.08
500 VA 1.03 0.97
550 VA 0.92 0.87
600 VA 0.83 0.78
700 VA 0.67 0.63
800 VA 0.54 0.55
900 VA 0.50 0.48
1000 VA 0.45 0.43
1200 VA 0.35 0.33
1400 VA 0.28 0.27
1600 VA 0.23 0.22
2000 VA 0.15 0.15
2200 VA 0.13 0.13
2500 VA - 0.10
3000 VA - 0.06
Page view 23