Caution:
Check the rack to make sure it won’t tip after moving the mounting brackets.
1. Determine where in the rack you’ll mount the UPS. The SU5000
requires a space of 5U. Some racks have tick marks to indicate
the U-spaces.
2. Using the mounting template provided (part number 990-0195),
identify and mark the correct mounting holes for the UPS
mounting brackets.
3. Locate and mark the bottom hole in the designated U-space Œ.
The bottom screw on the mounting rail will attach to the bottom
hole in the U-space.
4. Repeat steps 2 and 3 for the remaining three rack posts.
5. Prepare the rack holes, if necessary. Racks with threaded holes
require no preparation.
If your rack has round holes, insert clip nuts (provided) into
the holes marked in step 2.
If your rack has square holes, insert either clip or cage
nuts into the holes marked in step 2.
1
Remove the two screws Πthat hold the rails together so
that the rails can slide outward . Do not detach the rails.
2
Front
Align the bottom hole on the mounting rail with the bottom
hole in the U-space (marked in step 3 above). Use the flat,
Phillips head screws (10-32) and conical washers to attach
the front rail to the rack. Position the rails so that the lip of
the rail is on the bottom.