System earthing arrangements >
34020846EN/AD - Page 24
1. Installation
1.4 System earthing arrangements
This section lists the main SEAs (system earthing arrangements) and their wiring requirements. For SEAs not listed here,
please contact the technical-support department.
Single UPS system
TNS upstream, TNS downstream
For separate normal and bypass AC lines from a single source.
Without residual-current protection
With residual-current protection
UPS units used as frequency converters: please contact your technical assistance
Galvanic isolation between the normal and bypass AC lines is mandatory.
The recommended minimum residual current protection is 3A, provided the conditions defined in IEC364.4-41 are
respected.
For a transformer on a Bypass AC network
For a transformer on a Normal AC network
Adding a transformer into the Normal AC network reduces the installation’s overall yield.
Bypass AC
Normal AC
L1
L2
L3
L1
L2
L3
N
L1
L2
L3
N
Load
PE
SS
UPS
PFC
INV
PE
MLVS
PE
Bypass AC
Normal AC
L1
L2
L3
L1
L2
L3
N
L1
L2
L3
N
(4p)
Load
PE
SS
UPS
PFC
INV
PE
MLVS
PE
Bypass AC
Normal AC
L1
L2
L3
L1
L2
L3
N
L1
L2
L3
N
Load
PE
SS
PFC
INV
PE
MLVS
PE
Page view 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 63 64

Comments to this Manuals

No comments