Connecting the power cables > SSC cabinet
34020846EN/AD - Page 34
1. Installation
1200 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Key
(1) Front protective covers
(2) Roof protective covers
(3) Earthing bar
(4) To the earth
(5) To the UPSs*
(6) To bypass AC line
(7) To the load
Connections through the top of the
UPS cabinets are possible using an
auxiliary cabinet 400 mm wide.
1. Remove the protective covers (1)
and/or (2).
*Or to the SSC maintenance cabinet.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1. Check that switches Q4S, Q3BP
and Q5N are in the OFF position as
shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the UPS conductors taking
care to respect the order, N*, L1, L2,
L3.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
7. Put the protective covers back in
place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
A
A
3
5
7
7
6
6
1
1
1
1
1
2
4
OFF
OFF
OFF
6
7
Connection through the top
Connection through the bottom
Right-hand view
Front view
Top view
Front
view
N L1 L2 L3
N L1 L2 L3
N L1 L2 L3
559
807
1270
Q4S
Q3BP
Q5N
OFF
OFF
OFF
UPSs Bypass Load
AC
Earth