1. Choose a location and install the temperature/humidity sensor. Avoid locations in direct sunlight
or other locations that may affect the sensor reading, such as near windows, room entrances, air
ducts, or other heat sources.
Note: When securing the sensor, tighten the tie wrap over the recessed channel of the
sensor casing.
Vertical rail installation. Firmly
install the sensor mount (25 x 25-mm
[1 x 1-in] cable tie mount) at the
location you selected. Then secure the
sensor with a tie wrap.
Door-mount installation. For racks
with a perforated door, use a tie wrap to
secure the sensor.
Wall-mount installation. For a rough
wall or porous surface, install the wall
anchor at the location you selected.
Then, secure the sensor mount to the wall anchor using the screw provided. For a smooth wall
or other smooth surface, firmly install the sensor mount (25 x 25-mm [1 x 1-in] cable tie
mount). Secure the sensor to the sensor mount using a tie wrap.
2. Route the sensor cord to the Rack Monitor 200.
If you mounted the sensor on the door, be sure the door is fully open when you route the sensor
cord.
The 4-m (13-ft) sensor cord can be extended to a maximum of 15 m (50 ft), using RJ-45
female-to-female couplings and standard CAT-5 cables.
3. Connect the sensor to the Rack Monitor 200 (see “How to Connect Sensors to Universal Sensor
Ports” on page 10).