Apc SILCON 10-40KW 400V UPS User Manual Page 86

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 85
86 Installation Guide APC Silcon 10-40kW 400V UPS
990-4050
System Specifications
7.0 System Specifications
7.1 Technical Data
7.2 Back-up Time / Dimensions / Weigh
Voltage 3x380/400/415V
Input Voltage tolerance
Normal operation
Bypass operation
+15%
+10% (standard)
+4, 6, 8% (programmable)
Frequency 50Hz/60Hz
+6 standard
+0.5-8% (programmable)
Input power factor load 25% minimum 0.97
load 100% minimum 0.99
Current distortion Max. 5%
Output Voltage 3x380/400/415V
Voltage tolerance +
1% static symmetrical load
+3% static symmetrical load
+5% 0-100% load step
Voltage distortion max. 3% linear load
max. 5% non-linear load
Load power factor 0.9 lead to 0.8 lag
Frequency 50Hz/60Hz (mains synchronized)
+0.1% free-running
Overload capacity
Mains operation
Mains operation
Battery operation
Bypass operation
200% - 60 seconds
125% - 10 minutes
150% - 30 seconds
125% - continuous
General Ambient temperature 0-40
o
C (Temperatures above 25
o
C will
reduce battery lifetime)
Humidity
Protection class
Safety
Emission and Immunity
Static bypass switch
Auto restart
Economy mode
Max. 95% non-condensing
IP30
EN 50091-1
CE Mark
EN 50091-2
Built-in
Programmable
Programmable
Type 10kW 20kW 40kW
Back-up time.
UPS with built-
in batteries
22 min. 50 min. 78 min. 8
min.
22
min.
35
min.
0
min.
8
min.
Height [mm] 1400 1400 1400 1400 1400 1400 1400 1400
Width [mm] 600 800 1000 600 800 1000 600 1000
Depth [mm] 800 800 800 800 800 800 800 800
Weight [kg] 385 550 755 400 585 765 285 650
Page view 85
1 2 ... 81 82 83 84 85 86 87 88 89 90

Comments to this Manuals

No comments