Safety – SAVE THESE INSTRUCTIONS
AIS® 3000 10-40kVA, 400V, Site Preparation and Installation Manual – 990-2258 3
WARNING!
When replacing a Battery Unit, replace with the same number of the: APC SYBT1
(always replace a whole Battery Module (4 Battery Units) at a time).
WARNING!
Only trained personnel familiar with the construction and operation of the equipment
and the electrical and mechanical hazards involved, may install and remove system
components.
CAUTION!
Wait until you are ready to power up the system before installing Battery Modules in the
UPS. Failure to do so can result in a deep discharge of the batteries and cause permanent
damage. The time from the battery installation time till the UPS is powered up should
not exceed 72 hours or 3 days.
For configurations including customer-supplied external batteries, refer to
manufacturers battery installation and maintenance instructions.