Output
Output Power Capacity 865 Watts / 1500 VA
Max Configurable Power 865 Watts / 1500 VA
Nominal Output Voltage 120V
Output Frequency (sync to mains) 60 Hz
Crest Factor 3 : 1
Waveform Type Stepped approximation to a sinewave
Output Connections
(2) NEMA 5-15R (Surge Protection)
(6) NEMA 5-15R (Battery Backup)
Input
Nominal Input Voltage 120V
Input Frequency 60 Hz +/- 3 Hz
Input Connections
NEMA 5-15P
Cord Length 1.83 meters
Input voltage range for main
operations
88 - 139V
Maximum Input Current 12A
Input Breaker Capacity 15A
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time 16 hour(s)
Replacement Battery APCRBC109
RBC™ Quantity 1
Typical Backup Time
at Half Load
11.7 minutes (432.5 Watts)
Typical Backup Time
at Full Load
3.1 minutes (865 Watts)