MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference24
Parallel System
Fuse and Breaker Sizes
380 V, 400 V, and 415 V
380 V, 400 V, and 415 V 3:1
Q1: Utility input Q4: System output
Q2: UPS output Q5: Static bypass input
Q3: Manual bypass
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Mains input Q1 (A)
1
16 25 35 50 63
Bypass input Q5 (A)1625355063
Output Q2 (A) 1625355063
1 Required upstream current protection: gL type fuse.
15 kVA 20 kVA 30 kVA 40 kVA
Mains input Q1 (A)
1
25 35 50 63
Bypass input Q5 (A)
1
75 100 150 200
Output Q2 (A) 75 100 150 200
1 Required upstream current protection: gL type fuse
XR Battery
Enclosure
(optional)
XR Battery
(optional)
UPS A
UPS B
Q
5
A
Q
5
B
Q
2
B
Q
4
Q
3
Q
2
A
Q
1
A
Q
1
B
Comments to this Manuals