MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference26
Minimum Breaker Settings
380 V, 400 V, and 415 V
380 V, 400 V, and 415 V 3:1
Duration
800% overload
bypass operation
150% overload
normal/battery
operation
125% overload
normal/battery
operation
Continuously
500 ms 60 s 10 min.
10 kVA
Mains input -
1
- - 16.4 A
Bypass input 121.5 A - - 16.7 A
Output 121.5 A 22.8 A 19 A 16.7 A
15 kVA
Mains input -
1
- - 24.6 A
Bypass input 182 A - - 25.1 A
Output 182 A 34.2 A 25.4 A 25.1 A
20 kVA
Mains input -
1
- - 32.5 A
Bypass input 244 A - - 33.4 A
Output 244 A 45.6 A 38 A 33.4 A
30 kVA
Mains input -
1
- - 49.1 A
Bypass input 364 A - - 50.1 A
Output 364 A 68.4 A 57 A 50.1 A
40 kVA
Mains input -
1
- - 65.6 A
Bypass input 487 A - - 66.9 A
Output 487 A 91.2 A 76 A 66.9 A
Note:1 For single mains systems, use the higher value of mains and bypass.
Duration
800% overload
bypass operation
150% overload
normal/battery
operation
125% overload
normal/battery
operation
Continuously
500 ms 60 s 10 min.
15 kVA
Mains input - - - 24.6 A
Bypass input 547 A - - 75 A
Output 547 A 103 A 86 A 75 A
20 kVA
Mains input - - - 32.5 A
Bypass input 730 A - - 100 A
Output 730 A 137 A 114 A 100 A
30 kVA
Mains input - - - 49.1 A
Bypass input 1094 A - - 150 A
Output 1094 A 205 A 171 A 150 A
40 kVA
Mains input - - - 65.6 A
Bypass input 1459 A - - 200 A
Output 1459 A 274 A 228 A 200 A