3MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
Default Settings
System settings (only updated when in load disconnect) Default setting
Nominal output voltage (ph-ph) 380/400/415 V
Frequency 50 Hz
Frequency self-detect mode Auto
Frequency range ±10 Hz
Frequency slew rate 1 Hz/s
Generator charge percentage 100%
Cyclic charge mode enabled Off
Auto start On
Parallel UPS number 1
No. of parallel UPSs 1
MBP present No
Shutdown mode (can only be set from service port) Never
Shutdown setting
Low battery duration 2 minutes
Shutdown delay 20 seconds
Turn on delay 0 seconds
Return of battery capacity 0%
Alarm settings
Load alarm threshold System power rating
Runtime alarm threshold 0 (disabled)
Parallel redundancy alarm threshold n+0 (disabled)
Other settings
Battery self test Off
External battery capacity 0 Ah
Display settings
Display language English
Display contrast 0
Display beeper state PwerFail+30
Display beeper volume Low
Display key click Off