SBP Operation
Smart-UPS
®
VT SBP with Power Distribution 10-30kVA, 208V, Installation Manual - 990-4198A 17
Battery back-up operation
The UPS will automatically transfer from normal operation to battery back-up operation in instances
when utility power is lost or degraded. The heavier line shows the flow of battery-supplied power
through the UPS and Q2. Be aware that this transfer of power CANNOT take place when the UPS is
operating in static bypass mode or bypass mode.
Static bypass mode
Static bypass is a temporary operating mode that becomes active during the process of transferring
from normal operation to bypass operation, or from bypass operation to normal operation.
Note
After transferring from normal operation to battery back-up operation, the SBP
switch settings are unchanged: Q1 and Q2 are ON, and Q3 is OFF.
AC
Input
UPS
Static
Bypass
Load
Panel
Q1
UPS Input
Q3
Bypass
Q2
UPS Output
Input
Output
O OFF
I ON
O OFF
I ON
O OFF
I ON
Battery
Note
The user interface on the UPS initiates static bypass mode during transfer from
normal operation to bypass operation. The SBP switch settings remain unchanged:
Q1 and Q2 are ON, and Q3 is OFF.
AC
Input
UPS
Static
Bypass
Load
Panel
Q1
UPS Input
Q3
Bypass
Q2
UPS Output
Input
Output
O OFF
I ON
O OFF
I ON
O OFF
I ON