9Smart-UPS X-Series Operation
Nominal Output
Voltage
230 V: 230 VAC
120 V: 120 VAC
230 V: 220, 230, 240
VA C
120 V: N/A
Set the nominal output voltage of the UPS on
battery. This is available on 230 V models
only.
Transfer
Sensitivity
High High, Low, Medium Select the level of sensitivity to power events
that the UPS will tolerate.
• High: The UPS will go on battery power
more often to provide the cleanest power
supply to the connected equipment.
• Low: The UPS will tolerate more
fluctuations in power and will go on battery
power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to High.
Low Battery
Warning
150 sec Set the value in
seconds
The UPS will emit an audible alarm when the
remaining runtime has reached this level.
Date of Last
Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off The UPS will mute all audible alarms if this is
set to Off or when the display buttons are
pressed.
Battery Self-
Test Interval
Setting
On start-up and
every 14 days since
the last test
• Never
• Start-up only
• Frequency of test
(days)
The interval at which the UPS will execute a
self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.
Function Factory Default Options Description