Smart-UPS X-Series Operation12
Connect all critical equipment to the same outlet group.)
2. Connect peripheral equipment to the Controllable Outlet Groups.
Nonessential equipment that should shut off quickly in the event of a power outage to
conserve battery runtime can be added to a short power-off delay
If equipment has dependent peripherals that must restart or shut down in a specific order, such
as an ethernet switch that must restart before a connected server, connect the devices to
separate groups
Equipment that needs to reboot independently from other equipment should be added to a
separate group
3. Use the Configuration menus to configure how the Controllable Outlet Groups will react in the
event of a power outage.
Customize the Controllable Outlet Groups and the UPS outlets
Use the Control menus to change the Controllable Outlet Groups and the UPS outlet settings.
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec Set the value in
seconds
The amount of time the UPS or Controllable
Outlet Group will wait between receiving the
command to turn on and the actual startup.
Turn Off Delay 0 sec Set the value in
seconds
The amount of time that the UPS or
Controllable Outlet Group will wait between
receiving the command to turn off and the
actual shut down.
Reboot Duration 4 sec Set the value in
seconds
The amount of time that the UPS or
Controllable Outlet Group must remain off
before it will restart.
Minimum Return
Time
0 sec Set the value in
seconds
The amount of battery runtime that must be
available before the UPS or Controllable
Outlet Group will turn on.
Load Shed On
Battery
Disabled • Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with
delay
•Disabled
When the unit switches to battery power, the
UPS can disconnect power to the Controllable
Outlet Groups to save runtime.
Configure this delay time, use the
LOAD SHED
T
IME WHEN ON BATTERY setting.
Load Shed Time
when On Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on
battery power before they will turn off.