Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U18
General settings
Configure these settings at any time, using the display interface, or the Network Management Web Interface.
Parameters Default Value Options Description
Config
Menu
UPS
Green Mode
Disabled Disable
Enable
Disable or enable Green mode operation
AC Setting
User Choice 230 V, 220 V, 240 V,
208 V
Set the output voltage for the UPS. This setting can
only be changed when the UPS output is off.
These settings may vary depending on the UPS
model.
Output Lower
Acceptable
Voltage
184 V for 208 V output
198 V for 220 V output
207 V for 230 V output
216 V for 240 V output
208 V - 169 to 184 V
220 V - 186 to 198 V
230 V - 195 to 207 V
240 V - 204 to 216 V
If the UPS input voltage is between the lower
acceptable voltage and the higher acceptable
voltage, the UPS will operate in Green mode when
enabled.
If the output voltage goes outside the acceptable
range the UPS will switch from Green mode to On-
Line mode or to Battery mode.
Output Upper
Acceptable
Voltage
220 V for 208 V output
242 V for 220 V output
253 V for 230 V output
264 V for 240 V output
208 V - 220 to 235 V
220 V - 242 to 253 V
230 V - 253 to 265 V
240V - 264 to 270 V
Output
Frequency
Auto 50/60 ± 3Hz Auto 50/60 ± 3 Hz
50 ± 0.1 Hz
50 ± 3.0 Hz
60 ± 0.1 Hz
60 ± 3.0 Hz
Set the output frequency for the UPS.
Output
Frequency
Slew Rate
1 Hz/Sec 0.5 Hz/Sec
1 Hz/Sec
2 Hz/Sec
4 Hz/Sec
Select the rate of change for output frequency in
Hertz per second.
Bypass Lower
Acceptable
Voltage
160 V 208 V - 160 to 184 V
220 V - 160 to 198 V
230 V - 160 to 207 V
240V - 160 to 216 V
If the UPS input voltage is between the lower
acceptable voltage and the higher acceptable
voltage, the UPS can enter Bypass mode when
enabled.
Bypass Upper
Acceptable
Voltage
250 V for 208 V output
255 V for 220 V output
265 V for 230 V output
270 V for 240 V output
208 V - 220 to 250 V
220 V - 242 to 264 V
230 V - 253 to 270 V
240 V - 264 to 270 V
Bypass Mode
Allow Wider Frequency Allow Wider Frequency
Follow Frequency
Setting
The setting Allow Wider Frequency, enables
Bypass mode operation for an input frequency
range of
47-63 Hertz.
Low Runtime
Warning
150 seconds 0 to 1800 seconds The UPS will emit an audible alarm when the
remaining runtime has reached this threshold.
Self Test
Schedule
Startup + every 14 days
since last test
Never
Startup
Startup + 14 days
Startup + 7 days
This is the interval at which the UPS will execute a
Self Test.
Default Setting
No Yes/No Allows the user to restore the UPS factory default
settings.
Reset Energy
Meter
No Yes/No The Energy Meter stores information on UPS
output energy usage.
The Reset feature allows the user to reset the
Energy Meter to 0 kWh.