APC SU3000RMXLI3U User Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 25
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
16
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
High Transfer
Point
120V Models
132 VAC
230V Models
253 VAC
120V Models
138, 135, 129 VAC
230V Models
264, 271, 280 VAC
To avoid unnecessary battery usage, set
the high transfer point higher if the
utility voltage is chronically high and
the connected equipment is known to
work under this condition.
Low Transfer
Point
120V Models
103 VAC
230V Models
196 VAC
120V Models
97, 100, 106 VAC
230V Models
188, 204, 208 VAC
Set the low transfer point lower if the
utility voltage is chronically low and
the connected equipment can tolerate
this condition.