24 Installation Guide APC BC300 Series 40kW 208/450/480V UPS
990-1401
Installation
3.5.4.4 Triple Chassis Power Considerations
The Triple Chassis receives its power from the UPS through the supplied 24 VDC universal
adapter. The total current required by your management products
must not exceed the 850 mA
limit of the power adapter. See Determining power requirements.
3.5.4.5 Determining Power Requirements
To determine the total amount of current required by your management products, add the
individual current requirements for each management product to be installed with the APC
BC300 Triple Chassis to the current requirements of the chassis itself.
3.5.5 Troubleshooting
The following table shows the solutions to common problems with the operation of the Triple
Chassis
3.5.5.1 If Problems Persist
For problems not covered in the troubleshooting chart or for persistent problems, follow this
procedure:
Management Product Draw (mA)
Share-UPS 8-port Interface Expander 65
Expansion Chassis 30
Triple Chassis 20
APC BC300 Triple Chassis 90
Web/SNMP Management Card 110
Interface Expander 45
Out-of-Band Management Card 35
Environmental Monitoring Card 60
Isolated Extension Cable 50
Remote Power-Off Device 35
Problem Possible Cause Solution
Status LED is off The chassis is not
receiving adequate
power.
See Powering the APC BC300
Triple Chassis, and verify that you
are not exceeding current
requirements.
Status LED is flashing
quickly
The chassis has not been
configured.
Configure the Silcon Triple Chassis.
See the Web/SNMP Management
Card Installation Guide on the CD
for more information.
Status LED is flashing
slowly
The chassis is not
communicating with the
UPS.
Verify that the supplied UPS cable is
properly connected to the Triple
Chassis and to a communications
port on the UPS.
Attached management
product cannot identify
UPS model or nominal
output voltage.
The management
firmware does not
support 3-phase UPSs.
You may be able to upgrade the
firmware of the management
product. Call APC Customer
Support.