33User Guide InfraStruxure 150kVA Power Distribution Unit
sysOutput
Access: Administrator, Device
Description: View each phase-to-phase voltage, each phase-to-neutral voltage, load supported by each
phase and the frequency. Output measurements are made at the transformer.
Example:
apc> sysOutput
1. L1-L2,0V,L2-L3,0V,L3-L1,0V
2. L1,119V,19.4A,2.4kW,1.0,L2,119V,22.9A,2.7kW,1.0,L3,118V,21.1A,2.6kW,1.0
3. 60.0Hz
sysAlrmCfg
Access: Administrator, Device
Description: View the configuration of the system alarm thresholds.
Display order:
• Maximum output voltage threshold and enable
• High output voltage threshold and enable
• Low output voltage threshold and enable
• Minimum output voltage threshold and enable
• Maximum current threshold and enable
• High current threshold and enable
• Low current threshold and enable
• Minimum current threshold and enable
• Frequency Deviation enable
Example:
apc> sysAlrmCfg
1. MaxV,+20%,Disable,HiV,+12%,Disable,LoV,-12%,Disable,MinV,-20%,Disable
2. MaxA,0%,Disable,HiA,0%,Disable,LoA,0%,Disable,MinA,0%,Disable,Freq,
Disable