APC InRow Specifications Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
990-4618C-001 InRow Chilled Water Air Conditioners Technical Specifications 7
Configurations
Chilled water systems utilize water from a chiller plant for cooling. Chilled water is commonly used in large
buildings and high rises and can serve multiple indoor units, which can be cost effective for large installation
options. There are various methods for chilled water piping.
Connection to chiller through CDU
Note: Install isolation valves and particulate strainers with 20 mesh stainless steel screen (opening size = 865 micron) in the
supply line between the chiller and CDU. For more information, see the InRow Installation Manual.
*PEX-AL-PEX Piping and CDU are optional products available through Schneider Electric. For more information, see the
CDU Technical Data Manual.
**Piping between Chiller and CDU will vary based on local codes and site conditions.
***Top piping connection is an optional configuration for this unit: bottom piping is the standard configuration.
Direct connection to chiller
Note: Install isolation valves and particulate strainers with 20 mesh stainless steel screen (opening size = 865 micron) in the
supply line between the chiller and RC.
Item Description Item Description
InRow RC
Strainer**
Interconnecting PEX-AL-PEX Piping*
Valve**
Cooling Distribution Unit (CDU)*
(ACRC301S only)
Chiller
Item Description Item Description
InRow RC
Chiller
Valve
Strainer
na1993a
CONNECTION
SHOWN IS TOP
PIPING***
na2826a
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 103 104

Comments to this Manuals

No comments