APC InRow Specifications Page 67

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 66
990-4618C-001 InRow Chilled Water Air Conditioners Technical Specifications 61
Performance Data—General
ACRC301S
Maximum flow rate is 4720 l/hr (20.8 GPM) for continuous operation.
Maximum working pressure for the unit is 2068.4 kPa (300 psig).
†Maximum distance includes the maximum lift.
*Example: Performance at 29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB) with a 7.2°C (45°F) EWT, and a 5.5°C (10°F) CW
delta T is 21.8 kW (74000 BTU/hr) (total net capacity) with the standard filter. Using a 50-mm (2-in) pleated filter with single
fan failure, the performance of the unit would be 21.8 X 0.94 = 20.5 kW (74000 X .94 = 69560 BTU/hr).
MODULATING VALVES
Size 3 Way Ball Valve – NPT mm (in.) (Cv) 25.4 (1) (30.8)
AIR SYSTEM
200-mm (7.9-in)
MIXED FLOW DIRECT DRIVE DC
TUBEAXIAL FANS
Standard Filter 51-mm (2-in.) Pleated Filter
Air Volume - l/s (SCFM) 1510 (3200) 1345 (2850)
Fan Motor - Watts (each) 112.5 122.5
Number of Fans 8 8
Performance Specifications Table
Multiplier*
1.0 .94
WATER TEMPERATURE
Minimum Entering Temperature - ºC (ºF) 5 (41)
Maximum Entering Temperature - ºC (ºF) 15 (55.4)
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
(ft
2
) 0.510 (5.5)
Rows Deep 3
Face Velocity - m/s (FPM) 2.95 (582)
FILTERS - WASHABLE (STANDARD)
Quantity 2
Size - mm (in.) 238 x 933 (9.375 x 36.75)
Depth - mm (in.) 12.7 (1/2)
Efficiency (%) <20% MERV 1
FILTERS - PLEATED (OPTIONAL)
Quantity 2
Size - mm (in.) 238 x 933 (9.375 x 36.75)
Depth - mm (in.) 51 (2)
Efficiency (%) 30% MERV 8
PHYSICAL DATA
Net Weight - kg (lbs) 184 (406)
Operating Weight – kg (lbs) 192 (423)
Height - mm (in.) 1991 (78.39)
Width - mm (in.) 300 (11.81)
Depth - mm (in.) 1095 (43.11)
CONNECTION SIZES
Chilled Water
Supply Line - mm (in.) 25.4 (1) NPT Connection
Return Line - mm (in.) 25.4 (1) NPT Connection
Condensate Drain Drain Line - mm (in) 4.77 (3/16) ID, 6.35 (1/4) OD
DUAL FLOAT CONDENSATE MANAGEMENT
Flow Rate- L/hr (GPH) 5 (1.3)
Maximum Distance - m (ft)
15.2 (50)
Maximum Lift - m (ft) 4.9 (16)