14 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Control type
The controller utilizes proportional/integral/derivative (PID) settings, a time-proven precision environmental
control method. This allows for custom tuning of control variables to achieve optimal system response.
Functions
• Supply and Return Air Conditions
• Operational Mode Control
• Data Logging (ACRC301 series)
• Event Logging
• Alarms
• Redundant Group Control
• Fan Speed Adjustment
• Input/Output Module Programming
Logging
The event log keeps a record of all alarms and events. Each event log contains a time/date stamp as well as
operating conditions at the time of occurrence. The controller also displays run time, in hours, for major
components (air filters, fans, power supplies, and condensate pump).
The data log displays measurements about the cooling unit, the power input to the cooling unit, and the
ambient temperature of the cooling unit.
Control
The touch-screen LCD display interface provided on ACRC301S/ACRC301H units is protected by a
configurable password and provides access to information and settings for the unit.
• Supply Temperature Setpoint 15–30.2°C
(59–86.4°F)
• Cool Setpoint 18–35°C
(64.4–95°F)
• Rack Inlet High Temperature Threshold 10–65.6°C (50–150.1°F)
• Entering Chilled Water High Temperature Threshold 1.7–37.8°C (35–100°F)
• Supply Air High Temperature Threshold 10–65.6°C (50–150.1°F)
• Return Air High Temperature Threshold 10–65.6°C (50–150.1°F)
The backlit, four-line by twenty-character display interface provided on the ACRC500/ACRP500 series units
is protected by a configurable password.
• Supply Temperature Setpoint 15–30.2°C (59–86.4°F)
• Rack Inlet Temperature Setpoint 18–32°C (64.4–90°F)
• Rack Inlet High Temperature Alarm 0–100°C (32–212°F)
• CW Inlet High Temperature Alarm 0–37.7°C (32–100°F)
• Air Supply Temperature High Alarm 0–100°C (32–212°F)
• Return Temperature High Alarm 0–100°C (32–212°F)