5Automatic Transfer Switch—Installation and Quick Start
Installation
Mounting options
Horizontal mounting. You can mount the Rack ATS in a APC NetShelter
®
or other EIA-310-D
standard 19-in rack:
1. Choose a mounting position for the Rack
ATS with either the digital display or the rear
panel facing out of the enclosure.
2. Attach the mounting brackets to the Rack
ATS using the provided flat-head screws.
3. Choose a location for the unit:
a. Insert cage nuts above and below a notched
hole on each vertical mounting rail in your
chosen location.
b. Align the mounting holes of the brackets with
the installed cage nuts. Insert and tighten
screws.
Recessed horizontal mounting. You can mount the Rack ATS in a recessed configuration by
attaching the brackets as shown in the following illustration of the Rack ATS.
pdu0352a
pdu0353a
Note: The unit occupies one or two
U-spaces. A notched hole (or a number,
on newer enclosures) on the enclosures
vertical rail indicates the middle of a
U-space.
pdu0369a