A-5
If you select MANUAL skip the next four sections. If you select AUTO then continue with the next four
sections by pressing the
Down Arrow key.
Press the
System Setup button to advance to the GEN START RELAY POS, and GEN STOP RELAY POS
displays.
Generator Start and Stop Relay Positions
The generator is automatically started by closing a set of relay contacts. These settings are used to ensure
proper automatic start/stop operation based on the specific operating requirements of your generator. The
default is
NORMALLY OPEN.
Press the
System Setup button to advance to the GEN START DLY TIME and GEN STOP DLY TIME displays.
Note The automatic start/stop generator must have an automatic choke, and must be
capable of being started and stopped automatically from a remote location. Refer
to your generator user’s manual; if you are still unsure, contact the generator
manufacturer.
Also, to take full advantage of the automatic start/stop capability, we strongly
recommend that you use a UPS as the BACKUP2 source. If you do not have a UPS,
you cannot control the delays or relay positions of the start/stop relays if a power
failure should occur, and proper operation during a power outage cannot be
guaranteed.
Warning Operating a gas generator inside a building or any other enclosed area may result
in asphyxiation or death from breathing carbon monoxide. Locate the generator
outdoors away from doors and windows. Ensure the generator has 3 to 4 feet of
spacing on all sides, including above the generator. Generators need an unlimited
supply of fresh air for proper cooling during operation. If the generator uses
gasoline, ventilation is critical and fuel must be stored in containers approved for
gasoline storage. Ensure that the generator is kept dry and is always operated on a
solid, level surface.
Note
The UTS Automatic Remote Start/Stop Kit (UTS REM) is required for automatic
generator start/stop operation.
Caution Thoroughly review your generator user’s manual for the manufacturer’s
recommended installation guidelines, and contact your electrician to ensure it is
installed properly. APC provides a UTS Generator Hard Wiring Interfacing Kit
(UTSHW) that can be connected to the generators of manufacturers with whom
APC has jointly performed tests. A UTS Automatic Remote Start/Stop Kit
(UTSREM) is also available from APC to connect to a generator capable of remote,
automatic start/stop operation.
!
!
!
!
GEN START RELAYPOS:
NORMALLY OPEN/CLOSED
GEN STOP RELAY POS:
NORMALLY OPEN/CLOSED