Start-Up Procedure
58 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
When the System Enable switch is in the ON position, the UPS is running on battery. The Startup screen
appears on the display interface of the Symmetra PX UPS, and then
the top-level status screen appears on the display interface. This may take up to 40 seconds.
3. Read the messages displayed on the Symmetra PX UPS display interface:
Note any alarms and verify that they are
appropriate for start-up conditions.
Top-Level Status Screen
1. Command the UPS to apply power to the load:
a. Press the
ESC key to open the top-level
menu.
b. Select Control, and press the
ENTER key.
Top- Level Men u
a. Select Tur n Lo ad O n/ O ff from the
Control menu, and press the
ENTER key.
Control Menu
a. On the next screen: select Yes, UPS Load
ON, and press the
ENTER key.
Confirmation Screen
The interface will display the following screen:
PowerView RM
Rev: 000 English
Please wait...
Fuel %
Load %
Runtime:
||||||||||||
|||
1hr 2m
In 208V out000V 60Hz
Fuel %
Load %
Runtime:
||||||||||||
|||
1hr 2m
In 208V out000V 60Hz
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS Load ON
No, Abort
UPS has been
commanded to turn
load power on...