InRow RC Operation and Maintenance10
Start the cooling unit
Path: Main > On/Standby
1. To start the cooling unit, press the ENTER key until the cursor is on the Operation>On/Standby
menu item.
2. Press the
ENTER key again to show the toggle state arrow to the right of Operation.
3. Use the up and down arrow keys to change from Standby to On.
See “Path: Main > Operation> Limit Access” below if you are prompted to enter a
password before changing the On/Standby setting.
4. Press the
ENTER key again to set the On position.
a. The fans will start.
b. The cooling unit will run according to the configured settings.
Note: On/Standby only affects the local cooling unit. You must set the On/Standby option
for each cooling unit in the cooling group.
Path: Main > Operation> Limit Access
The default setting for the Limit Access password protection option is No. If the Limit Access option
has been set to Yes, you will be prompted to enter the Device password before a change can be made to
the On/Standby setting.
Stop the cooling unit
1. To stop the cooling unit, press the ENTER key until the cursor is on the Operation>On/Standby
menu item.
2. Press the
ENTER key again to show the toggle state arrow to the right of Operation.
3. Use the up and down arrow keys to change from On to Standby.
See “Path: Main > Operation> Limit Access” above if you are prompted to enter a
password before changing the On/Standby setting.
4. Press the
ENTER key again to change the setting to Standby. The cooling unit will enter the
standby mode.
Electrical Hazard: The Standby option does not remove power from the cooling unit. You
must disconnect power at the mains to remove power from the cooling unit.