®®990-1546, English, January 2004®®Symmetra LX200/208/230 V, 4–16 kVAOperations ManualSymmetra LX200/208/230 V, 4–16 kVAOperations ManualSymmetra LXRa
CHAPTER 3: MENU COMMANDS 8 3. Remove the screws securing the display bracket to the PowerView. 4. Disconnect the UPS cable from the RJ-45 po
CHAPTER 3: MENU COMMANDS 9 Command Reference The following sections describe the details of each command. Commands are organized according to the
CHAPTER 3: MENU COMMANDS 10 Display Menu The Display menu lets the user customize the PowerView display. Display Function Options Date/Time Set
CHAPTER 3: MENU COMMANDS 11 Diagnostics Menu The Diagnostics menu provides information for use in troubleshooting. Menu Item Function Fault and
CHAPTER 3: MENU COMMANDS 12 Logging Menu (continued) Menu Item Function List Event Groups Lists the specific events in each group. Power Events
CHAPTER 3: MENU COMMANDS 13 Setup Menu The Setup menu lets the user customize the UPS functionality. Menu Item Function Options Shutdown Sets t
CHAPTER 3: MENU COMMANDS 14 Setup Menu (continued) Menu Item Function Options Alarms Sets the alarm thresholds. None Redundancy An audible al
CHAPTER 4: MESSAGES 15 Troubleshooting The PowerView reports various messages on the display, including alarm status and changes in system configur
CHAPTER 4: MESSAGES 16 PowerView Message Meaning Corrective Action AC adequate for UPS but not for bypass. The UPS will function on-line with
CHAPTER 4: MESSAGES 17 PowerView Message Meaning Corrective Action Redundancy Restored. Power module redundancy loss occurred and was restore
TABLE OF CONTENTS Copyright and Trademark Information Entire contents copyright © 2004 by APC Corporation. All rights reserved. Reproduction in whole
CHAPTER 4: MESSAGES 18 PowerView Message Meaning Corrective Action Redundancy is below alarm threshold. Actual power module redundancy has fall
CHAPTER 4: MESSAGES 19 PowerView Message Meaning Corrective Action On Battery. The UPS is in the on-battery mode. The battery modules are be
CHAPTER 4: MESSAGES 20 PowerView Message Meaning Corrective Action Input circuit breaker tripped open. The input circuit breaker on the UPS tr
CHAPTER 5: MAINTENANCE 21 Service If the UPS requires service, do not return it to the dealer! Follow these steps: 1. Review the problems discusse
CHAPTER 1: OVERVIEW 1 PowerView Figure 1: Typical PowerView Display This manual contains information on how to operate the UPS using the PowerVi
CHAPTER 1: OVERVIEW 2 Functions Figure 2: Display Panel PowerView includes an alphanumeric display, navigation keys, status indicators, and an au
CHAPTER 3: MENU COMMANDS 3 Turning on the UPS Follow the steps below to turn ON the UPS. • The factory default Monitoring screen is
CHAPTER 3: MENU COMMANDS 4 Powering Up the Load Equipment Follow the steps below to turn ON the output of the UPS and power the load equipment.
CHAPTER 3: MENU COMMANDS 5 Powering Down the Load Equipment Follow the steps below to turn OFF the output of the UPS and power down the load equip
CHAPTER 3: MENU COMMANDS 6 Bypass Operation The bypass operation can be performed manually using the Maintenance Bypass Switch, or automatically us
CHAPTER 3: MENU COMMANDS 7 Bypass Operation (continued) Maintenance Bypass Procedure: The UPS Maintenance Bypass switch is also used to supply powe