APC SmartSlot Series Operations Instructions Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
Power Adapter
Next connect the optional power adapter (APC part number AP9505,
not supplied, for 100/120 Vac s
y
stems onl
y
), if required. The power
adapter is required under the followin
g
conditions:
To use the SmartSlot Expansion Chassis with an
y
Smart-UPS with a
serial number prior to S9405, an
y
Smart-UPS with a serial number
startin
g
with the letter W, and all Smart-UPS 250s.
With Matrix-UPS products when remote turn-on of the UPS is
required.
Contact the APC Customer Service Department at the number on the
back cover to obtain a power adapter if needed.
Decide whether to plu
g
the AC adapter into a wall outlet or a protected
UPS outlet. If the device powered b
y
the adapter needs to function
durin
g
a power outa
g
e, like for the pa
g
in
g
feature of the Remote UPS
Mana
g
ement Device (Call-UPS II), then plu
g
the power adapter into
one of the AC outlets on the UPS. If remote turn-on operation is
required with a Matrix-UPS, plu
g
the power adapter into a wall outlet.
See the operation check (section 4) before installin
g
an
y
UPS acces-
sor
y
in the Expansion Chassis.
3. Status Light
The SmartSlot Expansion Chassis status li
g
ht indicates the followin
g
states:
State Indication
Bri
g
ht Accessor
y
installed and Ex
p
ansion Chassis has
p
ower.
Dim Accessor
y
not installed and Ex
p
ansion Chassis has
p
ower.
Off No
p
ower to Ex
p
ansion Chassis.
Page view 5
1 2 3 4 5 6 7 8 9 10 11 12

Comments to this Manuals