9 NetShelter SX Cabinet - Installation and Customization Manual
Ground the Cabinet
Each cabinet should be bonded directly to a common ground using one of the designated grounding locations (two
M6 threaded inserts) at the top or bottom of the cabinet.
Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit® RGCBNJ660PY or equivalent).
Use paint-piercing washers between the ground terminal and the cabinet frame, or remove the paint on the frame
under the ground terminals, per NEC NFPA 70 Article 250.12.
Torque the screws to 6.9 N•m (60 lb-in).
Bonding Locations on the Cabinet
DANGER
HAZARD OF ELECTRIC SHOCK
Connection of the cabinet to building Common Bonding Network (CBN) is required.
Failure to follow these instructions will result in death or serious injury.